Title :
Power conditioning of a 132 MW wind farm
Author :
Plotkin, Juriy ; Hanitsch, Rolf ; Schaefer, Uwe
Author_Institution :
Berlin Univ. of Technol., Berlin
Abstract :
A possible reason for a low power quality at the output of a 132 MW wind farm is investigated. A resonant circuit formed by the wind farm components is found to be responsible for a high level of the dominating 7th current harmonic. Various compensation strategies are proposed and analyzed.
Keywords :
power system harmonics; power system measurement; wind power plants; 7th current harmonic; low power quality; power 132 MW; power conditioning; resonant circuit; wind farm; Pollution measurement; Power conditioning; Power generation; Power harmonic filters; Power measurement; Power quality; Power system harmonics; Voltage; Wind energy; Wind farms; Active filter; Passive filter; Power Quality; Power conditioning; Wind energy;