Factors affecting the commutation reactance of direct connected generator-converter units
Author :
Dinh, Q.N. ; Arrillaga, J.
Author_Institution :
Dept. of Electr. & Electron. Eng., Canterbury Univ., Christchurch, New Zealand
fDate :
31 Jan-4 Feb 1999
Abstract :
Summary form only as given. The effect of generator subtransient reactance, rotor saliency, the number of generators in the group connection configuration and adjustable speed operation on the commutation reactance and harmonic levels of direct connected units are examined. Restriction limits for firing angles imposed by the commutation angle, generator terminal power factor, equivalent continuous negative-sequence harmonic loading are derived that permit the use of normal generators in direct connected units without the need for extra harmonic loading capacity. The generator harmonic ratings can be taken at the nominal speed and rated power output.
Keywords :
commutation; electric generators; electric reactance; harmonic distortion; machine theory; power conversion harmonics; rotors; adjustable speed operation; commutation angle; commutation reactance; equivalent continuous negative-sequence harmonic loading; firing angles; generator harmonic ratings; generator subtransient reactance; generator terminal power factor; group connection configuration; harmonic levels; harmonic loading capacity; nominal speed; rated power output; rotor saliency; Power generation; Power system harmonics; Reactive power; Rotors;