DocumentCode :
2595869
Title :
Mechanical defect detection of SF6 high voltage circuit breaker using wavelet based vibration signal analysis
Author :
Charbkeaw, N. ; Suwanasri, T. ; Bunyagul, T.
Author_Institution :
Dept. of Electr. Eng., King Mongkut´´s Univ. of Technol. North Bangkok, Bangkok
Volume :
2
fYear :
2008
fDate :
14-17 May 2008
Firstpage :
901
Lastpage :
904
Abstract :
High voltage circuit breaker is a device that requires frequent maintenance. This leads to high cost and time consuming. If the internal component of circuit breaker can be inspected without any disassembly. The period of the maintenance can be extended. This paper proposes the method of indirect internal component inspection. The experiment was applied with 110 kV SF6 puffer-type circuit breaker with hydraulic operating mechanism. The defect circuit breakers were tested. Then the vibration signals were recorded. The analyzing of vibration signal in time domain is difficult for the detection of small defect. Using wavelet transform, the detection of small defect can be performed. This detection reduces the risk of the failure in operation of circuit breaker.
Keywords :
SF6 insulation; circuit breakers; signal detection; wavelet transforms; SF6; high voltage circuit breaker; hydraulic operating mechanism; mechanical defect detection; puffer-type circuit breaker; time domain; vibration signal analysis; voltage 110 kV; wavelet transform; Circuit breakers; Circuit testing; Costs; Inspection; Signal analysis; Sulfur hexafluoride; Time domain analysis; Vibrations; Voltage; Wavelet analysis;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology, 2008. ECTI-CON 2008. 5th International Conference on
Conference_Location :
Krabi
Print_ISBN :
978-1-4244-2101-5
Electronic_ISBN :
978-1-4244-2102-2
Type :
conf
DOI :
10.1109/ECTICON.2008.4600576
Filename :
4600576
Link To Document :
بازگشت