Abstract :
This paper describes the investigation of the insulation condition of a number of power and distribution type transformers of different manufacturing dates and with different operating histories. Return voltage measurements were conducted for these transformers. Effects of moisture and ageing on the oilpaper insulation of these transformers were investigated and results are presented in this paper. Moisture in oil samples at known temperature was measured for these transformers. Previously accelerated ageing experiments were performed on paper wrapped insulated conductors in different environments over a temperature range of 115 to 145°C. Results from the measurements on transformers are compared with those of the accelerated aged samples and are described in this paper.
Keywords :
ageing; condition monitoring; dielectric measurement; dielectric polarisation; impregnated insulation; insulation testing; moisture; molecular weight; power transformer insulation; transformer oil; voltage measurement; 115 to 145 C; condition monitoring; dielectric measurement; distribution type transformers; insulation life; molecular weight; oilpaper insulation ageing; oilpaper insulation moisture; polarization; power transformers; return voltage measurements; transformer insulation; wrapped insulated conductors; Accelerated aging; Conductors; History; Moisture measurement; Oil insulation; Petroleum; Power transformer insulation; Pulp manufacturing; Temperature measurement; Voltage measurement;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society General Meeting, 2003, IEEE
Print_ISBN :
0-7803-7989-6
Type :
conf
DOI :
10.1109/PES.2003.1271006
Filename :
1271006
Link To Document :
بازگشت