DocumentCode :
2604173
Title :
Effects of distribution generator on feeder automation and its solution
Author :
Lei, Wu ; Yuqin, Xu ; Li, Zhang
Author_Institution :
Power Eng. Dept., North China Electr. Power Univ., Baoding, China
fYear :
2009
fDate :
6-7 April 2009
Firstpage :
1
Lastpage :
5
Abstract :
In a distribution network with a distributed generator (DG), when a short-circuit fault occurs, the magnitude and direction of fault current may be different from the fault current of distribution network without DG. Under this circumstance, the cooperation of recloser and sectionalizer or fuses might be lost. This paper analyzes these misoperations and proposes new setting principles and calculating methods of the DG´s penetration level to ensure the correct isolation and clearing of fault.
Keywords :
distributed power generation; distribution networks; power system faults; distributed generator; distribution generator; distribution network; feeder automation; short-circuit fault; Automation; Character generation; Circuit faults; Distributed power generation; Fault currents; Fault detection; Power supplies; Protection; Wind energy generation; Wind turbines; distributed generator; distribution network; fault isolation; feeder automation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Sustainable Power Generation and Supply, 2009. SUPERGEN '09. International Conference on
Conference_Location :
Nanjing
Print_ISBN :
978-1-4244-4934-7
Type :
conf
DOI :
10.1109/SUPERGEN.2009.5348258
Filename :
5348258
Link To Document :
بازگشت