• DocumentCode
    2608365
  • Title

    Test Study on Corona Onset Voltage of UHV Transmission Lines Based on UV Detection

  • Author

    Yun-peng, Liu ; Hui-bin, Wang ; Wei-Jiang, Chen ; Ying-jian, Yang ; Jian, Tang

  • Author_Institution
    Sch. of Electr. & Electron. Eng., North China Electr. Power Univ., Wuhan
  • fYear
    2008
  • fDate
    9-12 Nov. 2008
  • Firstpage
    387
  • Lastpage
    390
  • Abstract
    Corona discharge is being detected by UV imaging detection technology at home and abroad in recent years. This technology is used in the corona tests of bundled conductors in this paper. In order to further research the corona characteristic, optimize geometry parameters and diameter of sub-conductor, and increase corona onset voltage of transmission lines, corona tests of three mode conductors which are placed inside the outdoor corona cage are conducted. Corona cage could be used to simulate the corona activities on transmission lines under a low voltage and different conditions in an effective and economical way. Photon which was created by UV light as a result of corona discharge on conductors is detected by the UV detection apparatus. The photon number within unit interval, namely photon counting rate is adopted as the parameter of quantifying the intensity of corona discharge. According to the apparent change of photon number, corona onset voltage can be judged. All tests are conducted under almost same atmosphere condition. Using the method, corona onset voltage is acquired. The results indicate that the tests have a good repeatability, in other words, repeat same test twice can acquires same result. The corona onset voltage can be acquired exactly from the curve of applied voltage vs. photon counting rate. Therefore UV detection apparatus can not only used to find discharge point exactly, but also applied on corona discharge research and live detection for power equipments. The method using in this paper is proved that is a new available method.
  • Keywords
    corona; high-voltage techniques; multiconductor transmission lines; power transmission lines; ultraviolet detectors; UHV transmission lines; UV imaging detection technology; corona discharge detection; corona onset voltage; geometry parameter optimisation; photon counting rate; three mode conductors; Atmosphere; Conductors; Corona; Instruments; Power engineering and energy; Power generation economics; Power transmission lines; Testing; Transmission lines; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    High Voltage Engineering and Application, 2008. ICHVE 2008. International Conference on
  • Conference_Location
    Chongqing
  • Print_ISBN
    978-1-4244-3823-5
  • Electronic_ISBN
    978-1-4244-2810-6
  • Type

    conf

  • DOI
    10.1109/ICHVE.2008.4773954
  • Filename
    4773954