DocumentCode
2608392
Title
Study on Characteristics of ±800kV DC Composite Insulators
Author
Bing, Luo ; Li Licheng ; Hong, Rao ; Li Xiaolin
Author_Institution
China Southern Power Grid Co., Ltd., Guangzhou, China
fYear
2008
fDate
9-12 Nov. 2008
Firstpage
394
Lastpage
398
Abstract
This paper presents the basic structure parameters of 800 kV DC composite insulator specimen and the pollution test scheme under whole voltage and whole structure dimension. The condition of 800 kV DC composite insulator pollution test under whole 800 kV voltage and whole structure dimension completed in STRI, which is completed first time in the world, is introduced. The study results indicate that the linear relation between the flashover voltage and the length of 800 kV DC composite insulator is high-blooded. The consistency of test data between STRI and CEPRI is good. The flashover characteristics of I string and V string under whole voltage and whole structure dimension is confirmed. The formula of DC pollution flashover grads calculated by SDD of DC composite insulator is obtained.
Keywords
HVDC power transmission; composite insulators; flashover; insulator contamination; insulator testing; CEPRI; DC composite insulator; SDD; STRI lab; UHVDC transmission system; flashover characteristics; pollution test scheme; voltage -800 kV to 800 kV; Contamination; Design optimization; Flashover; Insulation; Insulator testing; Pollution; Power engineering and energy; Power grids; Power transmission lines; Voltage; UHVDC; composite insulator; flashover characteristics;
fLanguage
English
Publisher
ieee
Conference_Titel
High Voltage Engineering and Application, 2008. ICHVE 2008. International Conference on
Conference_Location
Chongqing
Print_ISBN
978-1-4244-3823-5
Electronic_ISBN
978-1-4244-2810-6
Type
conf
DOI
10.1109/ICHVE.2008.4773956
Filename
4773956
Link To Document