• DocumentCode
    2608392
  • Title

    Study on Characteristics of ±800kV DC Composite Insulators

  • Author

    Bing, Luo ; Li Licheng ; Hong, Rao ; Li Xiaolin

  • Author_Institution
    China Southern Power Grid Co., Ltd., Guangzhou, China
  • fYear
    2008
  • fDate
    9-12 Nov. 2008
  • Firstpage
    394
  • Lastpage
    398
  • Abstract
    This paper presents the basic structure parameters of 800 kV DC composite insulator specimen and the pollution test scheme under whole voltage and whole structure dimension. The condition of 800 kV DC composite insulator pollution test under whole 800 kV voltage and whole structure dimension completed in STRI, which is completed first time in the world, is introduced. The study results indicate that the linear relation between the flashover voltage and the length of 800 kV DC composite insulator is high-blooded. The consistency of test data between STRI and CEPRI is good. The flashover characteristics of I string and V string under whole voltage and whole structure dimension is confirmed. The formula of DC pollution flashover grads calculated by SDD of DC composite insulator is obtained.
  • Keywords
    HVDC power transmission; composite insulators; flashover; insulator contamination; insulator testing; CEPRI; DC composite insulator; SDD; STRI lab; UHVDC transmission system; flashover characteristics; pollution test scheme; voltage -800 kV to 800 kV; Contamination; Design optimization; Flashover; Insulation; Insulator testing; Pollution; Power engineering and energy; Power grids; Power transmission lines; Voltage; UHVDC; composite insulator; flashover characteristics;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    High Voltage Engineering and Application, 2008. ICHVE 2008. International Conference on
  • Conference_Location
    Chongqing
  • Print_ISBN
    978-1-4244-3823-5
  • Electronic_ISBN
    978-1-4244-2810-6
  • Type

    conf

  • DOI
    10.1109/ICHVE.2008.4773956
  • Filename
    4773956