The Analysis of Secondary Arc Extinction Characteristics on UHV Transmission Lines
Author :
Baina, He ; Xin, Lin ; Jianyuan, Xu
fYear :
2008
fDate :
9-12 Nov. 2008
Firstpage :
516
Lastpage :
519
Abstract :
One of the important operational conditions of a single-circuit transmission line is the reclosing of circuit breaker, which depends on the value of secondary arc current. This paper presents the major methods of suppressing secondary arc current in ultra-high-voltage power transmission system. When the high speed earthing switch is adopted, the effect of secondary arc is studied. The magnitude of the secondary arc current and recovery voltage in arc path are obviously reduced after installing high speed earthing switch on line, which in turn reduces the extinction time of the secondary arc and assures successful single-phase auto reclosure. The arc affects the single-phase reclosing time of an ultra-high-voltage power transmission line, which is investigated on the basis of the secondary arc models.
Keywords :
circuit breakers; circuit-breaking arcs; earthing; power transmission lines; power transmission protection; UHV transmission line; circuit breaker reclosure; high speed earthing switch; recovery voltage; secondary arc current extinction characteristics; ultra-high-voltage power transmission system; Capacitance; Circuit breakers; Coupling circuits; Distributed parameter circuits; Grounding; Power transmission lines; Switches; Transmission lines; Voltage; Wire; High Speed Earthing Switch; Recovery voltage; Secondary arc; Simulation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
High Voltage Engineering and Application, 2008. ICHVE 2008. International Conference on
Conference_Location :
Chongqing
Print_ISBN :
978-1-4244-3823-5
Electronic_ISBN :
978-1-4244-2810-6
Type :
conf
DOI :
10.1109/ICHVE.2008.4773986
Filename :
4773986
Link To Document :
بازگشت