    Failure analysis of dry type power transformer

  • Author

    Paul, Dev

  • Author_Institution
    Kaiser Eng., Oakland, CA, USA
  • Volume
    5
  • fYear
    2000
  • fDate
    2000
  • Firstpage
    3232
  • Abstract
    This paper provides the failure analysis of three phase, dry type, silicone resin vacuum pressure encapsulated, 750/1000 kVA, AA/FA, 34.5 kV-480 Y/277 V, delta-wye, power transformer. Transient overvoltage switching surge propagation through the transformer winding and protection margin is discussed. An arbitrary sensitivity of 10 pico-coulombs (pc) at 120% rated voltage generally used for the partial discharge tests at the factory may be inadequate for the design of the failed transformer
  • Keywords
    encapsulation; failure analysis; overvoltage; partial discharge measurement; power transformer protection; power transformer testing; silicone insulation; surges; transformer windings; transients; 1000 kVA; 277 V; 3.45 kV; 480 V; 750 kVA; delta-wye power transformer; dry type power transformer; failed transformer; failure analysis; partial discharge tests; silicone resin vacuum pressure encapsulation; three phase; transformer winding; transient overvoltage switching surge propagation; vacuum pressure impregnation; Failure analysis; Partial discharges; Power system modeling; Power system transients; Power transformers; Production facilities; Surge protection; Switches; Testing; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Conference, 2000. Conference Record of the 2000 IEEE
  • Conference_Location
    Rome
  • ISSN
    0197-2618
  • Print_ISBN
    0-7803-6401-5
  • Type

    conf

  • DOI
    10.1109/IAS.2000.882629
  • Filename
    882629