DocumentCode :
2610216
Title :
Utilizing third harmonic 100% stator ground fault protection, a cogeneration experience
Author :
Rifaat, Rasheek M.
Author_Institution :
Delta Hudson Eng. Ltd., Calgary, Alta., Canada
Volume :
5
fYear :
2000
fDate :
2000
Firstpage :
3254
Abstract :
Third harmonic, 100% stator ground fault protection schemes are becoming economically viable for small and mid size generators used in cogeneration applications. Practical considerations must be observed in order that such schemes are successfully applied for different machines. This paper introduces an experience with the applications of 3rd harmonic schemes in cogeneration applications and depicts their advantages and limitations. For a 50 MVA generator, actual measurements of produced third harmonics are portrayed and analyzed. In light of the experience and analysis, applications of certain third harmonic scheme configurations are contemplated
Keywords :
AC generators; cogeneration; harmonics; machine protection; stators; voltage measurement; 3rd harmonic schemes; 3rd harmonic voltages measurement; 50 MVA; cogeneration; cogeneration machine protection; generator; mid size generators; small size generators; third harmonic stator ground fault protection; Application software; Cogeneration; Fault currents; Fault detection; Frequency; Grounding; Protection; Protective relaying; Stators; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industry Applications Conference, 2000. Conference Record of the 2000 IEEE
Conference_Location :
Rome
ISSN :
0197-2618
Print_ISBN :
0-7803-6401-5
Type :
conf
DOI :
10.1109/IAS.2000.882632
Filename :
882632
Link To Document :
بازگشت