• DocumentCode
    2610847
  • Title

    Installation of an integrated turbine-generator control system for a pulp mill

  • Author

    Weaver, Mark ; Hilder, Stephen ; Brown, David R.

  • Author_Institution
    Universal Dynamics Ltd., Richmond, BC, Canada
  • Volume
    5
  • fYear
    2000
  • fDate
    2000
  • Firstpage
    3468
  • Abstract
    A British Columbian pulp mill had experienced the “spiral of death” many times when the turbine-generator controls were unable to survive the loss of utility tie-line connections. The mill has two high efficiency rotary turbine-generator units rated 32.2 MVA each and a heat sink capable of generating 47 MW, approximately 87% of the mill power needs, though only 44 MW was being produced. The mill believed that with a load rejection strategy, the mill had the potential to continue operation after the loss of a utility tie. In order to ride through the loss of the utility and to fully utilize the process heatsink, the mill needed to replace the 1960s era turbine-generator control system supplied by the turbine-generator OEM. A triple modular redundant system for each unit was installed. These integrate turbine governor controls and generator excitation control system in a single digital control. The systems are connected in order to jointly coordinate dispatch of real and reactive power demands and achieve load control for the mill. In a staged test, the mill was able to survive the loss of a utility tie-line, and has increased total generation. The new system completely automates the startup, loading and synchronizing of both generators
  • Keywords
    industrial power systems; installation; load regulation; machine control; paper industry; power system control; project engineering; turbogenerators; 32.2 MVA; 44 MW; 47 MW; heat sink; installation; integrated turbine-generator control system; load control; load rejection strategy; loading; pulp mill; reactive power demand dispatch; real power demand dispatch; ride through; startup; synchronizing; triple modular redundant system; utility tie-line connections loss; Control systems; Digital control; Heat sinks; Load flow control; Milling machines; Power generation; Reactive power control; Temperature control; Testing; Turbines;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Conference, 2000. Conference Record of the 2000 IEEE
  • Conference_Location
    Rome
  • ISSN
    0197-2618
  • Print_ISBN
    0-7803-6401-5
  • Type

    conf

  • DOI
    10.1109/IAS.2000.882666
  • Filename
    882666