Title :
Development of the high accuracy Impedance Type Fault Locator using a Mode Transformation
Author :
Urano, Shoichi ; Yamada, Takeshi ; Ooura, Yoshifumi ; Xu, Youheng ; Yamaguchi, Yasutaka
Author_Institution :
Tokyo Electr. Power Co., Yokohama
Abstract :
The authors have developed an innovative FL (fault locator) system, which takes the 3-phase unbalance into consideration by simulation of a power transmission line with the distributed constant circuit and use of the theory of mode transformation. The system developed by the authors automatically reads the waveform data of voltage and current from the fault recorder which is time-synchronized to the GPS (global positioning system) and measures distance to the fault point using the above-mentioned data and power transmission system data which are set in advance. The authors carried out field tests of the FL System developed by the authors on fourteen lines of the 66 kV power transmission system of TEPCO (Tokyo electric power company) and obtained good results that showed a mean error of 0.43 [km]. This paper presents these results
Keywords :
Global Positioning System; fault location; power transmission faults; transmission line theory; 66 kV; GPS; TEPCO; Tokyo electric power company; distributed constant circuits; fault recorder; global positioning system; impedance type fault locator system; mode transformation theory; power transmission line; power transmission system data; Circuit faults; Circuit simulation; Current measurement; Global Positioning System; Impedance; Power measurement; Power transmission; Power transmission lines; Transmission line measurements; Voltage; Fault Locator (FL); Global Positioning System (GPS); Impedance type FL; Mode Transformation; distributed constant circuit; three-phase unbalanced transmission line;
Conference_Titel :
Transmission and Distribution Conference and Exhibition: Asia and Pacific, 2005 IEEE/PES
Conference_Location :
Dalian
Print_ISBN :
0-7803-9114-4
DOI :
10.1109/TDC.2005.1546890