Title :
Preventive maintenance testing of primary XLPE underground distribution cables and the application of the .1 Hz VLF test method
Abstract :
VLF testing is being considered as the safe alternative to DC Hipot testing of XLPE and mixed cables because of the known problem of induced space charges, which will cause premature failures in this type of cable. The IEEE work group 400.2 is working on a recommendation regarding the VLF test methodology. The paper compares different VLF technologies and discusses the correlation between field test data and test parameters
Keywords :
XLPE insulation; maintenance engineering; power cable testing; space charge; underground cables; underground distribution systems; 0.1 Hz; 0.1 Hz VLF test method; IEEE work group 400.2; VLF testing; XLPE cables; field test data; induced space charges; mixed cables; premature failures; preventive maintenance testing; primary XLPE underground distribution cables; test parameters; Cables; Electronic equipment testing; Frequency; IEC standards; Leakage current; Predictive maintenance; Preventive maintenance; Shape; Space charge; Space technology;