Title :
A Measure to Limit Secondary Arc and TRVs in Yangcheng Project
Author :
Xi, Jin ; Wei, Lu ; Pengyue, Lang
Abstract :
The successful single phase auto re-close (SPAR) depends on the self-extinction of secondary arc current. The neutral reactor in the neutral of shunt reactors is applied to reduce the electrostatic component of the secondary arc in the traditional transmission lines. The serial compensation changed the uniformity of the distributed parameters in the transmission lines. The mechanism of low frequency oscillation in the secondary arc of series compensated lines is analyzed in this paper. A measure to limit the secondary arc in series compensated lines is proposed, too and the validity is proved by simulation
Keywords :
arcs (electric); power transmission faults; power transmission lines; reactors (electric); SPAR; TRV; Yangcheng Project; distributed parameters; low frequency oscillation; neutral shunt reactors; secondary arc current; serial compensation; single phase auto reclose; transient recover voltage; transmission lines; Admittance; Capacitance; Circuit faults; Current measurement; Electrostatic measurements; Grounding; Inductance; Inductors; Power transmission lines; Voltage; SPAR; Transient Recover Voltage (TRV); secondary arc; serial compensation;
Conference_Titel :
Transmission and Distribution Conference and Exhibition: Asia and Pacific, 2005 IEEE/PES
Conference_Location :
Dalian
Print_ISBN :
0-7803-9114-4
DOI :
10.1109/TDC.2005.1546970