Abstract :
This study investigates ac EAFs by making field measurements; with those results indicate that the estimated DeltaV10 value obtained using the conventional method is significantly lower than the surveyed value. This paper found the DeltaQmax value of the original design is too small to respond the actual variation of reactive power. Meanwhile, the difference of DeltaQmax between design value and actual value is quite big. However, this investigation suggests that the DeltaQmax estimate calculation must adopt a stricter standard. Therefore, we refer to the operation experience of manufacturers, namely that the biggest value of Costhetasr equals 1.0 for ac EAFs. Furthermore, surveyed results reveal that the revised method can yield more accurate DeltaV10 estimates than traditional method
Keywords :
arc furnaces; current fluctuations; electric field measurement; power supply quality; reactive power; DeltaV10 value estimation; ac EAF; electric arc furnace; field measurement; power quality; reactive power; real-time measurement approach; voltage flicker; Fluorescent lamps; Furnaces; Manufacturing; Power quality; Power system modeling; Reactive power; Steel; TV; Voltage fluctuations; Yield estimation; EAF; Estimated AV; Voltage Flicker;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exhibition: Asia and Pacific, 2005 IEEE/PES
Conference_Location :
Dalian
Print_ISBN :
0-7803-9114-4
Type :
conf
DOI :
10.1109/TDC.2005.1547114
Filename :
1547114
Link To Document :
بازگشت