DocumentCode
2617748
Title
Analysis of Single-Phase-to-Ground Fault Generated Initial Traveling Waves
Author
Shi, Shenxing ; Dong, Xinzhou ; Zhou, Shuangxi
Author_Institution
Tsinghua Univ., Beijing
fYear
2005
fDate
2005
Firstpage
1
Lastpage
4
Abstract
Analysis of fault generated traveling waves is the base to implement traveling waves based protection and fault location. However, the structure at fault point is not asymmetrical under single-phase to ground fault condition in multi-phase power system, so that traveling waves analysis method of single circuit can not be applied. The paper at first analyzes initial traveling wave at fault point generated by the fault through resistance, according to superimposed theory and using phase-to-module transformation method, then considers the fault generated traveling waves´ characteristics at the relay point. At last, EMTP is implemented to verify the correctness of analysis of single-phase-to-ground fault generated initial traveling waves
Keywords
fault location; power system faults; power system protection; fault generated traveling waves; fault protection; ground fault location; multiphase power system; phase-to-module transformation method; single-phase-to-ground fault analysis; superimposed theory; traveling waves analysis method; Character generation; Circuit faults; EMTP; Fault location; Power system analysis computing; Power system faults; Power system protection; Power system relaying; Power transmission lines; Transmission line theory; fault analysis; single-phase-to-ground; traveling waves;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference and Exhibition: Asia and Pacific, 2005 IEEE/PES
Conference_Location
Dalian
Print_ISBN
0-7803-9114-4
Type
conf
DOI
10.1109/TDC.2005.1547176
Filename
1547176