DocumentCode :
2617748
Title :
Analysis of Single-Phase-to-Ground Fault Generated Initial Traveling Waves
Author :
Shi, Shenxing ; Dong, Xinzhou ; Zhou, Shuangxi
Author_Institution :
Tsinghua Univ., Beijing
fYear :
2005
fDate :
2005
Firstpage :
1
Lastpage :
4
Abstract :
Analysis of fault generated traveling waves is the base to implement traveling waves based protection and fault location. However, the structure at fault point is not asymmetrical under single-phase to ground fault condition in multi-phase power system, so that traveling waves analysis method of single circuit can not be applied. The paper at first analyzes initial traveling wave at fault point generated by the fault through resistance, according to superimposed theory and using phase-to-module transformation method, then considers the fault generated traveling waves´ characteristics at the relay point. At last, EMTP is implemented to verify the correctness of analysis of single-phase-to-ground fault generated initial traveling waves
Keywords :
fault location; power system faults; power system protection; fault generated traveling waves; fault protection; ground fault location; multiphase power system; phase-to-module transformation method; single-phase-to-ground fault analysis; superimposed theory; traveling waves analysis method; Character generation; Circuit faults; EMTP; Fault location; Power system analysis computing; Power system faults; Power system protection; Power system relaying; Power transmission lines; Transmission line theory; fault analysis; single-phase-to-ground; traveling waves;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exhibition: Asia and Pacific, 2005 IEEE/PES
Conference_Location :
Dalian
Print_ISBN :
0-7803-9114-4
Type :
conf
DOI :
10.1109/TDC.2005.1547176
Filename :
1547176
Link To Document :
بازگشت