• DocumentCode
    2621598
  • Title

    Fuel cell generator for telephone switching equipment

  • Author

    Ascoli, Aurelio

  • Author_Institution
    CISE Technol. Innovative SpA, Milan, Italy
  • fYear
    1989
  • fDate
    15-18 Oct 1989
  • Abstract
    As part of a wide on-site fuel-cell generator demonstration, 40 kW fuel cell systems were installed in 49 installations, including a telephone central office building in Connecticut. The authors describe the Connecticut installation and summarize the results of the demonstration project. The average operating time of the power plants was 6500 hours. One-third of the plants exceeding 8000 hours of operation, with the longest running unit operating for over 11000 hours. Total operating experience exceeded 300000 hours. Overall and electrical efficiencies were outstandingly stable over 8000 hours of operation with electrical at (40±1)% and overall at (70±10)%, with no visible performance degradation. This field test successfully demonstrated the features of utilities to host, operate, and maintain the equipment. High efficiency, low environmental impact quick load-variation response, performance stability, and suitability to power telephone switching equipment were demonstrated
  • Keywords
    fuel cells; power supplies to apparatus; telephone switching equipment; 40 kW; Connecticut; fuel-cell generator; performance stability; telephone switching equipment; Central office; Distributed power generation; Fuel cells; Heat recovery; Power industry; Space heating; Telephony; Temperature; Testing; Water heating;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 1989. INTELEC '89. Conference Proceedings., Eleventh International
  • Conference_Location
    Florence
  • Type

    conf

  • DOI
    10.1109/INTLEC.1989.88326
  • Filename
    88326