Title :
A distributed power supply system using new heat dissipation techniques
Author :
Chida, Jun ; Ohara, Hichimasa ; Satoh, Mitsuo ; Usui, Yoshinori
Author_Institution :
Fujitsu Ltd., Kawasaki, Japan
Abstract :
The authors describe a distributed power supply system for communication equipment. The system features a novel heat dissipation technique which uses a heat pipe and coupler. By adapting this system to a communications equipment system with four heat equipment subsystems which requires a total power of 400 W, it is possible to systematically reduce the power supply cost to about half of that of a conventional independent power supply system. The output power density in a shelf is five times that of the conventional power supply with heat sink,
Keywords :
cooling; power supplies to apparatus; telecommunication equipment; communication equipment; coupler; distributed power supply system; heat dissipation; heat pipe; output power density; Capacitors; Cooling; Costs; Heat sinks; Power conversion; Power generation; Power supplies; Power system reliability; Switching frequency; Thermal resistance;
Conference_Titel :
Telecommunications Energy Conference, 1989. INTELEC '89. Conference Proceedings., Eleventh International
Conference_Location :
Florence
DOI :
10.1109/INTLEC.1989.88359