  • Title

    Numerical modeling of the electric field in a 24 kV switchgear

  • Author

    Krajewski, W. ; Sibilski, H. ; Wojciechowski, R.

  • Author_Institution
    Electrotech. Inst., Warsaw, Poland
  • fYear
    2014
  • fDate
    8-11 Sept. 2014
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    In the paper, the electric field assessment in a selected compartment of a 24 kV switchgear produced by Polish company ZPUE SA is presented. In the considered switchgear, an insulation of SF6 will be substituted by a dry air insulation that is more ecological, however, it is of the lower dielectric withstand. The numerical computations have enabled to determine points of the maximum electric field strength in the considered switchgear compartment. Simple measures that enable to avoid insulation breakdown are proposed.
  • Keywords
    air insulation; switchgear insulation; Polish company ZPUE SA; SF6 insulation; dry air insulation; electric field assessment; electric field numerical modeling; insulation breakdown avoidance; lower dielectric withstand; maximum electric field strength; switchgear compartment; voltage 24 kV; Electromagnetic compatibility; Materials; Switches; Switchgear;
  • fLanguage
    English