Abstract :
In this paper, the Recurrent Plot (RP) method is used to monitor polluted insulator performance. LC acquisition is first carried out on 1512L insulator model, under various lengths (5, 10, 15, 20 and 25 cm) of a polluted layer deposited at HV side. Next, the high frequency component of LC is extracted and reconstructed in an appropriate phase space. RP is then computed. For a polluted layer length up to 15 cm, RP diagram consists in dispersed low density recurrent points indicating the faint discharge activity and thus, the healthy insulator condition. However, for a polluted layer length more up to 15 cm, RP is composed of intense recurrent points and wide white bands. The dense recurrent points indicate the apparition of stronger discharges, while the white bands announce the presence of arcing discharges on the insulating surface. RP technique, based on LC frequency representation, provides an efficient and rapid analysis of the insulator condition. RP represents an excellent alternative to classical signal processing methods for polluted insulator performance monitoring.
Keywords :
arcs (electric); insulator contamination; leakage currents; power transmission lines; signal processing; HV insulator model; LC acquisition; LC frequency representation; RP diagram; RP method; RP technique; arcing discharges; discharge activity; discontinuous pollution; leakage current investigation; phase space; recurrent plot method; signal processing methods; size 10 cm; size 20 cm; size 25 cm; size 5 cm; Monitoring; RNA;
Conference_Titel :
High Voltage Engineering and Application (ICHVE), 2014 International Conference on
Conference_Location :
Poznan
DOI :
10.1109/ICHVE.2014.7035444