DocumentCode :
2630087
Title :
On the development of transfer function method for fault identification in large power transformers on load
Author :
Pinhas, Nathan ; Islam, Syed ; Hullett, John
Author_Institution :
Sch. of Electr. & Comput. Eng., Curtin Univ. of Technol., Perth, WA, Australia
Volume :
2
fYear :
2000
fDate :
15-18 Oct. 2000
Firstpage :
747
Abstract :
Frequency Response Analysis (FRA) is now established as a proven tool in identifying some typical mechanical faults in power transformers. However, all FRA measurements so far have been off-line. An on-line technique is very much desired by the utilities, as this will prevent continued operation of the transformer while it is carrying a fault to failure stage. In this paper, challenges and some progress made so far toward the development of an on-line FRA technique has been presented. The paper also reports on the development of a high frequency magnetic coupler for this purpose. Results on some sensitivity analysis on a large reactor coil showing significant but characteristic changes on the FRA signatures to parameter variations. Observations of results obtained show that an on-line FRA tool is achievable but still there are some issues that need to be addressed.
Keywords :
fault diagnosis; frequency response; power transformer testing; sensitivity analysis; transfer functions; fault identification; frequency response analysis; high-frequency current transformer; magnetic coupler; on-line measurement; power transformer; reactor coil; sensitivity analysis; transfer function; Capacitance measurement; Current transformers; Fault diagnosis; Frequency response; Oil insulation; Power measurement; Power transformer insulation; Power transformers; Transfer functions; US Department of Transportation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2000 Annual Report Conference on
Print_ISBN :
0-7803-6413-9
Type :
conf
DOI :
10.1109/CEIDP.2000.884066