• DocumentCode
    263011
  • Title

    Partial discharge experiences in HV grids applying wideband measurements

  • Author

    Alvarez, F. ; Ortego, J. ; Garnacho, F. ; Sanchez-Uran, M.A. ; Prieto, D.

  • Author_Institution
    Polytech. Univ. of Madrid, Ronda, Spain
  • fYear
    2014
  • fDate
    8-11 Sept. 2014
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Different partial discharge (PD) measuring techniques have been developed in the last years specially designed to perform on-site and on-line measurements. When on-line PD measurements are performed in noisy environments or when more than one source of pulse-shaped signals is present in the test object, in many cases it results very difficult to perform a correct diagnosis. In order to provide reliable high level indicators of the insulation status, some challenges like noise discrimination, PD location and pattern identification have been considered in this study. Some practical experiences about on-line PD measurements in high voltage (HV) grids are presented. These PD measurements were addressed to improve the electrical system reliability using a modern measuring device operating in wideband frequencies. Insulation defects were found in time to avoid uncontrolled failures in the power grid.
  • Keywords
    partial discharge measurement; power grids; power system measurement; power system reliability; HV grids; electrical system reliability; high voltage grids; insulation defects; noise discrimination; partial discharge; power grid; pulse-shaped signals; wideband measurements; Noise; Noise measurement; Pulse measurements; Reliability; Substations; Switches; Synchronization;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    High Voltage Engineering and Application (ICHVE), 2014 International Conference on
  • Conference_Location
    Poznan
  • Type

    conf

  • DOI
    10.1109/ICHVE.2014.7035446
  • Filename