• DocumentCode
    263078
  • Title

    Probability distributions of gases dissolved in oil of failed power transformers

  • Author

    Piotrowski, T.

  • Author_Institution
    Inst. of Electr. Power Eng., Lodz Univ. of Technol., Lodz, Poland
  • fYear
    2014
  • fDate
    8-11 Sept. 2014
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    The author collected about 300 sets of measured concentrations of gases dissolved in the oil of power transformers. All were obtained by chromatographic analysis of oil samples taken from transformers with known actual defect. Defects were classified into one of three basic types: dischargers, partial discharges and thermal faults. The probability distributions of the individual gas concentrations, depending on the type of fault present in the transformer were identified. The values of heterogeneity coefficient and parameters of probability distributions were given. It has been shown that the gases dissolved in oil of fault transformers are subject of log-normal or Weibull probability distributions regardless of the type of the defect.
  • Keywords
    Weibull distribution; chromatography; failure analysis; fault diagnosis; partial discharges; power transformers; transformer oil; chromatographic analysis; dischargers; dissolved gas Weibull probability distribution; heterogeneity coefficient; partial discharge; power transformer failure; power transformer oil; thermal fault diagnosis; Discharges (electric); Gases; Oil insulation; Partial discharges; Power transformer insulation; Probability distribution;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    High Voltage Engineering and Application (ICHVE), 2014 International Conference on
  • Conference_Location
    Poznan
  • Type

    conf

  • DOI
    10.1109/ICHVE.2014.7035482
  • Filename
    7035482