• DocumentCode
    2633422
  • Title

    False trips on transformer inrush - avoiding the unavoidable

  • Author

    Ni, Raymond ; Wang, Peter ; Moxley, Roy ; Flemming, Stefan ; Schneider, Sebastian

  • Author_Institution
    ATCO Electr., USA
  • fYear
    2015
  • fDate
    March 30 2015-April 2 2015
  • Firstpage
    553
  • Lastpage
    556
  • Abstract
    The nature of the magnitizing circuit of a transformer requires that under some initial closing conditions there will be a significant current from the closing sourse; appearing to a differential relay as a difference current - a fault. Because, as the wave position at the instant of closing will vary, protection is complicated. Considering that a fault is possible at the moment of energization also adds complications. Over the years there have been a number of different schemes to avoid false tripping during transforer inrush. These have included increased pickup´s, time delays, harmonic blocking and harmonic restraint. Harmonic elements have been useful, as one characteristic of inrush has been a harmonic component.
  • Keywords
    delays; magnetic circuits; power system harmonics; power transformers; differential relay; energization moment; false tripping avoidance; harmonic blocking; harmonic component; harmonic restraint; initial closing conditions; magnitizing circuit; time delays; transformer inrush; wave position; Harmonic analysis; Power harmonic filters; Relays; Security; Surge protection; Surges; Windings; Differential; Harmonics; Inrush; Restraint; Waveform;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Protective Relay Engineers, 2015 68th Annual Conference for
  • Conference_Location
    College Station, TX
  • Print_ISBN
    978-1-4799-8721-4
  • Type

    conf

  • DOI
    10.1109/CPRE.2015.7102193
  • Filename
    7102193