• DocumentCode
    2635112
  • Title

    Field experience and pollution monitoring of composite long rod insulators

  • Author

    Lee, C.J.

  • Author_Institution
    Queensland Electr. Comm., Brisbane, Qld., Australia
  • fYear
    1995
  • fDate
    29-31 Mar 1995
  • Firstpage
    204
  • Lastpage
    209
  • Abstract
    The Queensland Electricity Commission (QEC) has 16 years of field experience with various types of composite insulators on 110 kV to 275 kV transmission lines. Most of the insulators were first generation composites installed in clean and contaminated environments. In heavily contaminated areas, various forms of damage to the sheath and sheds were observed and a number of insulators flashed over. These failures have also been experienced in other parts of the world. This paper describes field experience with composite insulators and a leakage monitoring program that was initiated to evaluate the new generation of composites. For the monitoring program, a sensitive high voltage leakage current monitor was developed and a highly contaminated test site was selected for testing these insulators. Five long rod insulators were monitored over a two year period: 2 ethylene propylene diene monomer insulators; and 3 silicon rubber insulators, and comparisons were made with a string of ceramic insulators
  • Keywords
    composite insulators; electric current measurement; electric sensing devices; failure analysis; flashover; insulator contamination; insulator testing; leakage currents; polymer insulators; power system measurement; power system reliability; power transmission lines; silicone rubber insulators; 110 to 275 kV; Australia; Queensland Electricity Commission; composite long rod insulators; contamination; ethylene propylene diene monomer; failures; field experience; flashover; leakage current monitor; leakage monitoring; pollution monitoring; sheath; sheds; silicon rubber; testing; transmission lines;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Reliability of Transmission and Distribution Equipment, 1995., Second International Conference on the
  • Conference_Location
    Coventry
  • Print_ISBN
    0-85296-628-8
  • Type

    conf

  • DOI
    10.1049/cp:19950243
  • Filename
    395989