DocumentCode
2635749
Title
A new approach for harmonics current extraction for non-linear loads
Author
Zaki, Areej M. ; Mansour, A.A. ; Mahgoub, O.A.
Author_Institution
Electron. Res. Inst., Cairo
fYear
2007
fDate
17-20 Sept. 2007
Firstpage
72
Lastpage
76
Abstract
The harmonic pollutions in the electrical networks became one of the major factors affecting the power quality of the network. APF´s represent the most convenient system used to eliminate harmonics. To achieve instantaneous harmonic compensation, the harmonic current reference should be extracted very fast. In this paper, the average technique is used to extract the harmonics current contents for a three-phase three-wires symmetric load using one current sensor. The current in one phase is recorded and saved in a look-up table to be used to generate the second phase.. The developed technique is verified by simulation and experimentally for nonlinear load distorted waveforms. This approach achieved excellent results to split the harmonic contents of the different nonlinear loads
Keywords
power supply quality; power system harmonics; table lookup; electrical network; harmonics current extraction; look-up table; nonlinear load distorted waveform; power supply quality; three-phase three-wire symmetric load; Active filters; Data mining; Frequency domain analysis; Operational amplifiers; Pollution; Power harmonic filters; Power quality; Power system harmonics; Silicon compounds; Table lookup;
fLanguage
English
Publisher
ieee
Conference_Titel
SICE, 2007 Annual Conference
Conference_Location
Takamatsu
Print_ISBN
978-4-907764-27-2
Electronic_ISBN
978-4-907764-27-2
Type
conf
DOI
10.1109/SICE.2007.4420953
Filename
4420953
Link To Document