Abstract :
The harmonic pollutions in the electrical networks became one of the major factors affecting the power quality of the network. APF´s represent the most convenient system used to eliminate harmonics. To achieve instantaneous harmonic compensation, the harmonic current reference should be extracted very fast. In this paper, the average technique is used to extract the harmonics current contents for a three-phase three-wires symmetric load using one current sensor. The current in one phase is recorded and saved in a look-up table to be used to generate the second phase.. The developed technique is verified by simulation and experimentally for nonlinear load distorted waveforms. This approach achieved excellent results to split the harmonic contents of the different nonlinear loads
Keywords :
power supply quality; power system harmonics; table lookup; electrical network; harmonics current extraction; look-up table; nonlinear load distorted waveform; power supply quality; three-phase three-wire symmetric load; Active filters; Data mining; Frequency domain analysis; Operational amplifiers; Pollution; Power harmonic filters; Power quality; Power system harmonics; Silicon compounds; Table lookup;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
SICE, 2007 Annual Conference
Conference_Location :
Takamatsu
Print_ISBN :
978-4-907764-27-2
Electronic_ISBN :
978-4-907764-27-2
Type :
conf
DOI :
10.1109/SICE.2007.4420953
Filename :
4420953
Link To Document :
بازگشت