• DocumentCode
    2636174
  • Title

    Research of current transformer analyzing system based on low-voltage approach

  • Author

    Liu, Tianyu ; Zuo, Tingtao ; Wang, Fei ; Hu, Xiaoguang

  • Author_Institution
    Sch. of Autom. Sci. & Electr. Eng., Beihang Univ., Beijing, China
  • fYear
    2011
  • fDate
    21-23 June 2011
  • Firstpage
    1074
  • Lastpage
    1078
  • Abstract
    A new type of current transformer (CT) calibration approach is introduced, which is based on the current transformer equivalent model. We can analysis the CT´s performance by calculating its internal parameters. The current transformer error, voltage characteristics, 10% error curve can be measured, solving the problem of up-flow unit and the standard current transformer is no longer needed in the on-site verification. It is more convenient for the users to carry out the field testing of current transformers.
  • Keywords
    calibration; current transformers; current transformer analyzing system; current transformer calibration; current transformer equivalent model; current transformer error; error curve; field testing; low-voltage approach; up-flow unit; Circuit faults; Current measurement; Current transformers; Magnetic flux; Magnetic hysteresis; Saturation magnetization; Windings; 10% error curve; current transformer; voltage characteristic;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial Electronics and Applications (ICIEA), 2011 6th IEEE Conference on
  • Conference_Location
    Beijing
  • ISSN
    pending
  • Print_ISBN
    978-1-4244-8754-7
  • Electronic_ISBN
    pending
  • Type

    conf

  • DOI
    10.1109/ICIEA.2011.5975746
  • Filename
    5975746