• DocumentCode
    2637187
  • Title

    STATCOM and UPQC: Options to enhance fault-ride-through capability of a fixed speed wind generator

  • Author

    Jayanti, N.G. ; Basu, M. ; Conlon, M.F. ; Gaughan, K.

  • Author_Institution
    Sch. of Electr. Eng. Syst., Dublin Inst. of Technol., Dublin, Ireland
  • fYear
    2012
  • fDate
    27-29 March 2012
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    The enhancement of fault-ride through (FRT) capability of a Fixed Speed Induction Generator (FSIG) with the help of a Unified Power Quality Conditioner (UPQC) and STATCOM are examined in this paper. The FRT performance of these equipments are evaluated and compared in accordance with Irish Grid Code requirement. A simulation study carried out on a 2 MW wind turbine with varying power system parameters has shown that the application of a STATCOM can be economical for a stronger networks where as a UPQC seems to be the economical option when the FSIG is connected to a weaker network.
  • Keywords
    asynchronous generators; power generation faults; power supply quality; static VAr compensators; wind power plants; wind turbines; FRT capability; FSIG; STATCOM; UPQC; fault ride through; fixed speed induction generator; power 2 MW; power system parameter variation; unified power quality conditioner; wind generator; wind turbine; FSIG; Fault-Ride-Through; STATCOM; UPQC; wind;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Power Electronics, Machines and Drives (PEMD 2012), 6th IET International Conference on
  • Conference_Location
    Bristol
  • Electronic_ISBN
    978-1-84919-616-1
  • Type

    conf

  • DOI
    10.1049/cp.2012.0191
  • Filename
    6242040