Title :
Application of TCR-Type SVC in power substation and electric arc furnaces
Author :
Zhao, ZhongYuan ; Chen, ChiHan ; Bao, ShunXian ; Fang, TaiXun ; Wang, XiaoHong
Author_Institution :
NanJing NARI-RELAYS Electr. Co. Ltd., Nanjing, China
Abstract :
The situation at electric arc furnace factory is always severe containing voltage fluctuation and flicker, three-phase imbalance and low power factor. The dynamic var compensator is a good solution to this condition. The svc, with its continuously variable compensation, also safeguards the plant against overcompensation during furnace outages. The svc equipment, offered by NARI-RELAYS, presents a phase-wise open-loop reactive power controller and a three-phase closed-loop power factor control, which are based on high-speed space vector control. The factory system test on physical simulator is implemented, and its open-loop response time is less than 7 milliseconds with closed-loop one less than 25 milliseconds. One electric arc furnace plant engineering is illustrated as an example to show the effects with/without SVC function. Meanwhile, the voltage fluctuation depression is also shown with SVC operation applied in a power substation.
Keywords :
Electric variables control; Furnaces; Open loop systems; Production facilities; Reactive power; Reactive power control; Static VAr compensators; Substations; System testing; Voltage fluctuations; SVC; electric arc furnace; harmonic mitigation; voltage fluctuation and flicker;
Conference_Titel :
Transmission and Distribution Conference and Exposition, 2010 IEEE PES
Conference_Location :
New Orleans, LA, USA
Print_ISBN :
978-1-4244-6546-0
DOI :
10.1109/TDC.2010.5484282