• DocumentCode
    2637800
  • Title

    Economic analysis and justification for transmission line transposition

  • Author

    Mooney, Joseph B.

  • Author_Institution
    P.E., POWER Engineers, Inc., USA
  • fYear
    2010
  • fDate
    19-22 April 2010
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    This paper shows a technique to economically justify transposition of a transmission line using the cost of the transposition towers versus the line losses for a transposed or non-transposed line over the in-service life of the line. This paper discusses and presents: 1. Background on transmission line transposition. 2. A method for calculating the three-phase line losses for unbalanced conditions. 3. A method for calculating the net present value of the line losses and comparing the line losses for a transposed versus untransposed line. 4. Case study comparison for two different transmission line configurations. The method shown in this paper provides the transmission line owner with the necessary tools to make an educated decision on transmission line transposition.
  • Keywords
    Conductors; Costs; Distributed parameter circuits; Impedance; Poles and towers; Power generation economics; Power transmission lines; Propagation losses; Transmission line matrix methods; Transmission lines; Impedance matrix; Load flow analysis; Losses;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exposition, 2010 IEEE PES
  • Conference_Location
    New Orleans, LA, USA
  • Print_ISBN
    978-1-4244-6546-0
  • Type

    conf

  • DOI
    10.1109/TDC.2010.5484296
  • Filename
    5484296