Title :
Adaptive distance protection in presence of STATCOM on a transmission line
Author :
Kazemi, A. ; Jamali, S. ; Shateri, H.
Author_Institution :
Dept. of Electr. Eng., Iran Univ. of Sci. & Technol. (IUST), Tehran, Iran
Abstract :
This paper presents an adaptive distance protection in the presence of STATic synchronous COMpensator (STATCOM), one of the shunt connected Flexible Alternating Current Transmission System (FACTS) devices. The presence of STATCOM on a transmission line has a great influence on the measured impedance at the relaying point. The measured impedance itself depends on the power system structural conditions, pre-fault loading, and especially the fault resistance. In the presence of STATCOM, its injected current as well as its installation point affects the measured impedance. Therefore, the conventional distance techniques could not fulfill the protective duties satisfactorily and new approaches are required.
Keywords :
Automatic voltage control; Electrical resistance measurement; Flexible AC transmission systems; Impedance measurement; Power system protection; Power system relaying; Power transmission lines; Protective relaying; Transmission line measurements; Transmission lines; Adaptive protection; Distance protection; FACTS devices; Fault resistance; Measured impedance; STATCOM;
Conference_Titel :
Transmission and Distribution Conference and Exposition, 2010 IEEE PES
Conference_Location :
New Orleans, LA, USA
Print_ISBN :
978-1-4244-6546-0
DOI :
10.1109/TDC.2010.5484350