DocumentCode
2638801
Title
Adaptive distance protection in presence of STATCOM on a transmission line
Author
Kazemi, A. ; Jamali, S. ; Shateri, H.
Author_Institution
Dept. of Electr. Eng., Iran Univ. of Sci. & Technol. (IUST), Tehran, Iran
fYear
2010
fDate
19-22 April 2010
Firstpage
1
Lastpage
6
Abstract
This paper presents an adaptive distance protection in the presence of STATic synchronous COMpensator (STATCOM), one of the shunt connected Flexible Alternating Current Transmission System (FACTS) devices. The presence of STATCOM on a transmission line has a great influence on the measured impedance at the relaying point. The measured impedance itself depends on the power system structural conditions, pre-fault loading, and especially the fault resistance. In the presence of STATCOM, its injected current as well as its installation point affects the measured impedance. Therefore, the conventional distance techniques could not fulfill the protective duties satisfactorily and new approaches are required.
Keywords
Automatic voltage control; Electrical resistance measurement; Flexible AC transmission systems; Impedance measurement; Power system protection; Power system relaying; Power transmission lines; Protective relaying; Transmission line measurements; Transmission lines; Adaptive protection; Distance protection; FACTS devices; Fault resistance; Measured impedance; STATCOM;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference and Exposition, 2010 IEEE PES
Conference_Location
New Orleans, LA, USA
Print_ISBN
978-1-4244-6546-0
Type
conf
DOI
10.1109/TDC.2010.5484350
Filename
5484350
Link To Document