• DocumentCode
    2641836
  • Title

    Automatic interconnecting system for photovoltaics and utility line

  • Author

    Murata, K. ; Harada, K.

  • Author_Institution
    Inf. & Electron. Eng., Yatsushiro Nat. Coll. of Technol., Japan
  • fYear
    1994
  • fDate
    30 Oct-3 Nov 1994
  • Firstpage
    658
  • Lastpage
    664
  • Abstract
    This paper describes a new interconnecting system for numerous photovoltaics and utility line. In this system, each of the DC-DC converters derives the maximum power from each of photovoltaics for any daylight strength. Outputs of converters are connected to a DC bus line. The inverter sends power from the DC bus line to the utility line. The inverter is automatically synchronized to the utility line by means of a phase locked loop which includes the inner resistance of the DC bus line. A power factor controller combined with the phase locked loop makes power factor unity by changing the output voltage of the inverter corresponding to total output power of the photovoltaics
  • Keywords
    DC-AC power convertors; DC-DC power convertors; invertors; phase locked loops; photovoltaic power systems; power factor correction; power system interconnection; DC bus line; DC-DC converters; automatic interconnecting system; inner resistance; inverter; phase locked loop; photovoltaics; power factor controller; unity power factor; utility line; DC-DC power converters; Educational institutions; Integrated circuit interconnections; Inverters; Phase locked loops; Photovoltaic cells; Power generation; Power system interconnection; Reactive power; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 1994. INTELEC '94., 16th International
  • Conference_Location
    Vancouver, BC
  • Print_ISBN
    0-7803-2034-4
  • Type

    conf

  • DOI
    10.1109/INTLEC.1994.396581
  • Filename
    396581