Title :
Development of UPS using new type of circuits
Author :
Hirachi, Kazuyuki ; Sakane, M. ; Niwa, S. ; Matsui, Takashi
Author_Institution :
Yuasa Corp., Osaka
fDate :
30 Oct-3 Nov 1994
Abstract :
Using a half-bridge converter and a half-bridge inverter respectively in the AC/DC conversion section and the DC/AC conversion section of an uninterruptible power supply (UPS) makes it possible to omit the isolating transformer and render the UPS both more efficient and smaller. But as using such a circuit necessitates storage batteries of very high voltage, it is in particular not suitable as a type of circuit for small-capacity UPSs of the 1 to 3 kVA class. We therefore conceived two techniques in order to lower necessary storage battery voltage: one that uses a bidirectional chopper, and one that uses an auxiliary, inverter. We incorporated these techniques into a 3 kVA UPS and a 1 kVA UPS respectively, allowing us to develop small, high-performance UPSs
Keywords :
AC-DC power convertors; DC-AC power convertors; bridge circuits; choppers (circuits); invertors; uninterruptible power supplies; 1 to 3 kVA; AC/DC conversion; DC/AC conversion; UPS; bidirectional chopper; half-bridge converter; half-bridge inverter; storage battery voltage reduction; uninterruptible power supply; Analog-digital conversion; Batteries; Choppers; Circuits; Pulse width modulation inverters; Reactive power; Silicon compounds; Uninterruptible power systems; Voltage control; Wire;
Conference_Titel :
Telecommunications Energy Conference, 1994. INTELEC '94., 16th International
Conference_Location :
Vancouver, BC
Print_ISBN :
0-7803-2034-4
DOI :
10.1109/INTLEC.1994.396585