    Grounding elbow with 25kA fault-closure rating for underground distribution systems

  • Author

    Hughes, David C.

  • Author_Institution
    Cooper Power Syst., Pewaukee, WI, USA
  • fYear
    2010
  • fDate
    19-22 April 2010
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    This paper details advancements in the grounding of dead-front underground distribution (UD) systems that yield safer operation and prevent outages. Standard 200 A grounding elbows for UD systems are rated for a maximum fault-closure of 10 kA. A very hazardous fault accompanied by flying bushing fragments will generally result if a fault-closure occurs above 10kA. Some utilities have been forced to push their 200 A systems above 10 kA; and many others are using 10 kA grounding elbows on their 600 A 25 kA rated systems. This paper documents the design, method, application, and test results of a grounding device rated for a 25 kA fault-closure operation. The device features a current limiting fuse that limits the energy and opens any fault with minimal energy let-thru. The current limiting fuse makes any fault-closure operation much safer for the operator and keeps customers in power by opening the fault.
  • Keywords
    Circuit faults; Connectors; Elbow; Fuses; Grounding; Insulators; Manufacturing; Safety; System testing; Voltage; Current; fault currents; fuses; grounding; power distribution; power distribution reliability; safety; switchgear; vacuum switches; voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exposition, 2010 IEEE PES
  • Conference_Location
    New Orleans, LA, USA
  • Print_ISBN
    978-1-4244-6546-0
  • Type

    conf

  • DOI
    10.1109/TDC.2010.5484668
  • Filename
    5484668