Grounding elbow with 25kA fault-closure rating for underground distribution systems
Author :
Hughes, David C.
Author_Institution :
Cooper Power Syst., Pewaukee, WI, USA
Abstract :
This paper details advancements in the grounding of dead-front underground distribution (UD) systems that yield safer operation and prevent outages. Standard 200 A grounding elbows for UD systems are rated for a maximum fault-closure of 10 kA. A very hazardous fault accompanied by flying bushing fragments will generally result if a fault-closure occurs above 10kA. Some utilities have been forced to push their 200 A systems above 10 kA; and many others are using 10 kA grounding elbows on their 600 A 25 kA rated systems. This paper documents the design, method, application, and test results of a grounding device rated for a 25 kA fault-closure operation. The device features a current limiting fuse that limits the energy and opens any fault with minimal energy let-thru. The current limiting fuse makes any fault-closure operation much safer for the operator and keeps customers in power by opening the fault.
Keywords :
Circuit faults; Connectors; Elbow; Fuses; Grounding; Insulators; Manufacturing; Safety; System testing; Voltage; Current; fault currents; fuses; grounding; power distribution; power distribution reliability; safety; switchgear; vacuum switches; voltage;