Abstract :
This paper describes the result of an investigation on the effect of air gap of core lamination in two 3-phase distribution transformers 1000 kVA. The investigation involves the variation of power loss, building factor, the third harmonic distortion and flux leakages. The power loss and flux distribution have been measured using no load test in two types of model of setting of core built from the same size and type of M5 (CGO) grades material of laminations. And the loss of the transformer core without air gap of layer joint of core lamination is 2.75% better than the loss of the transformer core with air gap of layer joint of core lamination at 1.7 T, 50 Hz. The flux leakage at the corner joint in the core without air gap of layer joint of lamination is lower than that in the transformer core with air gap of layer joint of lamination, over the whole flux density range. The third harmonic distortion of flux is smaller in the transformer core without air gap of layer joint of lamination and larger in the transformer core with air gap of layer joint of core lamination. Using the type without air gap of layer joint of lamination in transformer core is more efficient than the other types of transformer core lamination.
Keywords :
air gaps; harmonic distortion; transformer cores; 3-phase distribution transformers; air gap; apparent power 1000 kVA; building factor; flux density range; flux distribution; flux leakage; harmonic distortion; power loss; transformer core lamination; Assembly; Costs; Harmonic distortion; Iron; Lamination; Magnetic cores; Magnetic materials; Silicon; Steel; Transformer cores; Transformer core; flux distribution; power loss;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Applied Electromagnetics, 2007. APACE 2007. Asia-Pacific Conference on
Conference_Location :
Melaka
Print_ISBN :
978-1-4244-1434-5
Electronic_ISBN :
978-1-4244-1435-2
Type :
conf
DOI :
10.1109/APACE.2007.4603874
Filename :
4603874
Link To Document :
بازگشت