Abstract
On the east-coast of the Malaysia Peninsular, high voltage insulators of power plants and factories suffer from rapid salt contamination accumulation because of heavy wind coming from the South China Sea. One attempt has been made at one of these plants which is located about 500 meters from the seashore to determine the severity of this kind of contamination and subsequently to determine a suitable mitigation method to overcome this problem. This work describes a mathematical model, which could help to determine the contamination level. It has been proven that the contamination severity predictive model is possible by using a regression technique and it is a useful method for determining the Equivalent Salt Deposit Density (ESDD)
Keywords
insulator contamination; insulator testing; statistical analysis; 500 m; Malaysia Peninsular; South China Sea; contamination level; contamination severity predictive model; equivalent salt deposit density; factories; heavy wind; high voltage insulators; mathematical model; mitigation method; power plants; rapid salt contamination; regression technique; salt contamination severity; Contamination; Flashover; Humidity; Insulation; Meteorology; Ocean temperature; Pollution; Power system reliability; Voltage; Wind speed;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 2000 Annual Report Conference on
Conference_Location
Victoria, BC
Print_ISBN
0-7803-6413-9
Type
conf
DOI
10.1109/CEIDP.2000.885266
Filename
885266
Link To Document