• DocumentCode
    2658876
  • Title

    Current-limiting switching by squeezing arcs into narrow insulating slots

  • Author

    Lindmayer, Manfred ; Huang, Z.

  • Author_Institution
    Inst. fuer Energieanlagen, Tech. Univ. Braunschweig, Germany
  • fYear
    1991
  • fDate
    6-9 Oct. 1991
  • Firstpage
    44
  • Lastpage
    52
  • Abstract
    For low-voltage circuit breakers, arc breaking by squeezing the arc in a narrow insulating slot is an interesting alternative to the conventional technique of using arc chutes with steel plates. The performance of a switching device based on this principle was experimentally investigated. The influence of slot dimension, switching speed, insulating material, and other test parameters on the arc breaking characteristics was determined. The results show that the arc voltage in the slot chambers depends mostly on the arc length (moving speed of the plate) and the cross-sectional area of the slot, while the influence of the insulating material and the shape of the slot plays only a minor role. By using a simplified ar model the curves of arc voltage and arc current can be simulated. There is a good agreement between the experimental and the calculated results.<>
  • Keywords
    circuit breakers; circuit-breaking arcs; switchgear testing; ar model; arc breaking; arc current; arc length; cross-sectional area; insulating material; low-voltage circuit breakers; narrow insulating slots; slot dimension; switching speed; test parameters; Cathodes; Circuit testing; Crystalline materials; Insulation; Materials testing; Optical materials; Rough surfaces; Silver; Surface roughness; Welding;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Contacts, 1991. Proceedings of the Thirty-Seventh IEEE Holm Conference on
  • Conference_Location
    Chicago, IL, USA
  • Print_ISBN
    0-7803-0231-1
  • Type

    conf

  • DOI
    10.1109/HOLM.1991.170803
  • Filename
    170803