DocumentCode :
2659321
Title :
Measurement based fault location in three-terminal overhead line and underground cable
Author :
Fulczyk, M. ; Balcerek, P. ; Rosolowski, E. ; Izykowski, J. ; Saha, M.M.
Author_Institution :
ABB Corp. Res. Center, Krakow, Poland
fYear :
2010
fDate :
17-20 Oct. 2010
Firstpage :
1
Lastpage :
4
Abstract :
This paper presents a new fault location method for three-terminal composite network consisting of two overhead line sections and a cable. Synchronized measurements of three-phase current from all three ends and three-phase voltage - from the bus, where the fault locator (FL) is installed, are utilized for fault location. The fault location algorithm consists of three subroutines designated for locating faults within the respective line/cable sections and a multi-criteria procedure for selecting the valid subroutine. Generalized model of a fault loop are used for formulating the subroutines. Sample results of ATP-EMTP based evaluation are presented and discussed.
Keywords :
electric current measurement; fault location; power overhead lines; underground cables; voltage measurement; ATP-EMTP based evaluation; fault location; fault loop; multicriteria procedure; synchronized measurement; three phase current; three phase voltage; three terminal composite network; three terminal overhead line; underground cable;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena (CEIDP), 2010 Annual Report Conference on
Conference_Location :
West Lafayette, IN
ISSN :
0084-9162
Print_ISBN :
978-1-4244-9468-2
Type :
conf
DOI :
10.1109/CEIDP.2010.5724005
Filename :
5724005
Link To Document :
بازگشت