DocumentCode :
26602
Title :
A Distributed PMU for Electrical Substations With Wireless Redundant Process Bus
Author :
Castello, Paolo ; Ferrari, Paolo ; Flammini, Alessandra ; Muscas, Carlo ; Pegoraro, Paolo Attilio ; Rinaldi, Stefano
Author_Institution :
Dept. of Electr. & Electron. Eng., Univ. of Cagliari, Cagliari, Italy
Volume :
64
Issue :
5
fYear :
2015
fDate :
May-15
Firstpage :
1149
Lastpage :
1157
Abstract :
Protection and measurement systems in electrical substations are required to have high availability. In an all-digital substation protection system, all the components (instrument transformers, processing units, merging units, intelligent electronic devices, communication network, and synchronization source) may affect the overall availability level. In this paper, a solution to enhance distributed PMU availability, during wired network failures, is presented. In the proposed scheme, the process bus has two parallel networks: 1) the classic wired Ethernet link and 2) a wireless link (implemented with industrial grade IEEE 802.11 devices), for sampled values packets, which carry measurement information. The time synchronization is carried out only through the wired Ethernet link, but the proposed solution is still able to compensate temporary failures of one of the communication links. Experimental tests have been performed to verify the performance of additional IEEE 802.11 link using different protocols and configurations. Communication parameters that can affect the PMU performance, like propagation latency, are characterized. It is shown that, if the measurement algorithm is opportunely designed, depending on the wireless link quality, it is possible to comply, with a single output, with M and P classes of the synchrophasor standard also during network restoration or, at least, to safeguard protection applications if higher latency occurs.
Keywords :
distribution networks; phasor measurement; wireless LAN; IEEE 802.11 link; distributed PMU; electrical substations; measurement algorithm; phasor measurement unit; propagation latency; wired Ethernet link; wireless link; wireless redundant process bus; Availability; IEEE 802.11 Standards; Phasor measurement units; Substations; Synchronization; Wireless communication; Availability; IEEE 802.11; communication latency measure; hybrid network; phasor measurement unit (PMU); process bus; substation automation system (SAS); synchrophasor; wireless LAN; wireless LAN.;
fLanguage :
English
Journal_Title :
Instrumentation and Measurement, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9456
Type :
jour
DOI :
10.1109/TIM.2014.2363749
Filename :
6945856
Link To Document :
بازگشت