DocumentCode
2660926
Title
Early stage detection of insulating oil decaying
Author
Fofana, I. ; Bouaïcha, A. ; Hadjadj, Y. ; N´Cho, J.S. ; Aka-Ngnui, T. ; Béroual, A.
Author_Institution
Dept. of Insulating Liquids & Mixed Dielectr. for Electrotechnol. (ISOLIME), Univ. du Quebec a Chicoutimi, Chicoutimi, QC, Canada
fYear
2010
fDate
17-20 Oct. 2010
Firstpage
1
Lastpage
4
Abstract
It is an established fact that regular oil analysis is extremely useful in monitoring the condition of power transformers. To ensure long-term reliability of oil filled power transformers, it is important to identify the degradation characteristics of insulating oil in long-term operations, which are the dominant factors of the transformer dielectric strength. In this contribution, oil decaying was monitored with various ASTM test methods. Oil samples were submitted to thermal aging with oxygen inlet in laboratory conditions. Many key parameters providing a “picture” of the fluid have been determined. From the obtained results, some correlations were found between some of them. Dissolved decay products, which change with a higher rate than interfacial tension and total acid values, can be possibly used as an effective index for insulating oil degradation.
Keywords
condition monitoring; insulating oils; power transformer insulation; ASTM test method; condition monitoring; degradation characteristics; early stage detection; insulating oil decaying; insulating oil degradation; oil filled power transformer reliability; oxygen inlet; thermal aging; transformer dielectric strength; Aging; Oil insulation; Oxidation; Petroleum; Power transformer insulation;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena (CEIDP), 2010 Annual Report Conference on
Conference_Location
West Lafayette, IN
ISSN
0084-9162
Print_ISBN
978-1-4244-9468-2
Type
conf
DOI
10.1109/CEIDP.2010.5724098
Filename
5724098
Link To Document