Title :
Wind farms with increased transient stability margin provided by a STATCOM
Author :
Molinas, Marta ; Suul, Jon Are ; Undeland, Tore
Author_Institution :
Dept. of Electr. Power Eng., Norwegian Univ. of Sci. & Technol., Trondheim
Abstract :
This paper analyzes the extent to which the transient stability margin of wind farms using squirrel cage generators can be increased by the use of a STATCOM. A simplified analytical approach is used first to quantify the effect of the STATCOM on the transient stability margin. An experimental validation of the calculated transient margin is then presented by measurements done in a laboratory prototype of 7.5 kW emulating a wind turbine or wind farms. Measurement results confirm that the STATCOM provides a clear transient stability margin increase and with adequate rating it becomes possible to ride through severe faults
Keywords :
power supply quality; stability; static VAr compensators; wind power plants; wind turbines; 7.5 kW; STATCOM; squirrel cage wind generator; transient stability; vector control; voltage sag; voltage source static Var compensator; wind farms; wind turbine; Automatic voltage control; Circuit faults; Power system modeling; Power system stability; Power system transients; Stability analysis; Transient analysis; Wind energy generation; Wind farms; Wind turbines; Grid Code; Squirrel Cage Wind Generator; Transient Stability Margin; Vector Control; Voltage Sag; Voltage Source Static Var Compensator;
Conference_Titel :
Power Electronics and Motion Control Conference, 2006. IPEMC 2006. CES/IEEE 5th International
Conference_Location :
Shanghai
Print_ISBN :
1-4244-0448-7
DOI :
10.1109/IPEMC.2006.4777948