DocumentCode :
2661047
Title :
The assessment of oil-paper insulation condition based on frequency response method
Author :
Liu, Jun ; Wu, Guang-ning ; Lv, Wei ; Zhou, Li-jun ; Min, Ying-jie
Author_Institution :
Sch. of Electr. Eng., Southwest Jiaotong Univ., Chengdu, China
fYear :
2010
fDate :
17-20 Oct. 2010
Firstpage :
1
Lastpage :
4
Abstract :
For analysis of the status of oil-paper insulation, the dielectric response method was used to model oil-paper insulation system. Then the dielectric spectroscopy of oil-paper insulation system was tested. And the influence of oil gap on the test results of oil-paper insulation response was discussed. The results showed that the dielectric response method can effectively assess the status of oil-paper insulation, and the influence of oil gap on the test results is less than 10%.
Keywords :
insulation; dielectric response method; dielectric spectroscopy; frequency response method; oil gap; oil-paper insulation condition; oil-paper insulation response; oil-paper insulation system; Dielectric measurements; Dielectrics; Frequency response; Oil insulation; Petroleum; Power transformer insulation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena (CEIDP), 2010 Annual Report Conference on
Conference_Location :
West Lafayette, IN
ISSN :
0084-9162
Print_ISBN :
978-1-4244-9468-2
Type :
conf
DOI :
10.1109/CEIDP.2010.5724105
Filename :
5724105
Link To Document :
بازگشت