DocumentCode :
267333
Title :
The current and voltage detection under nonsinusoidal and unbalanced voltage condition
Author :
Xiaobin Zhang ; Pan Zhang ; Siyu Cheng ; Jiandong Duan ; Hui Zhang
Author_Institution :
Dept. of Electr. Eng., Xi´an Univ. of Technol., Xi´an, China
fYear :
2014
fDate :
5-8 Nov. 2014
Firstpage :
794
Lastpage :
799
Abstract :
The accurate and rapid detection of voltage and current in non-sinusoidal and unbalanced voltage condition is the prerequisite for grid power quality management and stable operation. Based on analyzing the vectors of the grid voltage and current, the rotating vector detection is carried out which can detect the voltage and current specified harmonic component and reactive and active current in non-sinusoidal and unbalanced voltage condition. The detection algorithm needs only the instantaneous value of voltage and current and no need the phase locking loop (PLL) to detect the voltage phase angle. The detection accuracy is not affected by the voltage frequency offset. The simulation results illustrate the accuracy of the rotating vector detection.
Keywords :
harmonic analysis; power supply quality; reactive power; PLL; active current; current detection; grid power quality management; harmonic component; nonsinusoidal voltage condition; phase locking loop; reactive current; rotating vector detection; unbalanced voltage condition; voltage detection; voltage frequency offset; voltage phase angle; Accuracy; Active filters; Filtering algorithms; Harmonic analysis; Mathematical model; Power harmonic filters; Vectors; detection; non-sinusoidal and unbalanced voltage; phase locking loop; rotating vector detection;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electronics and Application Conference and Exposition (PEAC), 2014 International
Conference_Location :
Shanghai
Type :
conf
DOI :
10.1109/PEAC.2014.7037959
Filename :
7037959
Link To Document :
بازگشت