DocumentCode
2677429
Title
Power active filter installation effect in three-phase four-wire distribution network
Author
Zemerov, G.G. ; Ilyina, N.A. ; Ilyina, O.V. ; Sokol, E.I. ; Tugay, D.V.
Author_Institution
Nat. Tech. Univ. "Kharkov Politechnical Inst.", Kharkov, Ukraine
fYear
2009
fDate
1-6 July 2009
Firstpage
395
Lastpage
400
Abstract
An active filter control strategy that uses pqr instantaneous power concept has been proposed to compensate for the harmonic distortion, line neutral current and reactive power in three-phase four-wire systems. The effectiveness of the proposed control was proved in simulations using Matlab/Simulink model of the power-supply system with an active filter where the harmonic pollution, reactive power and imbalance caused by a highly distorting load have been drastically reduced.
Keywords
active filters; electric current control; harmonic distortion; installation; power distribution control; power harmonic filters; reactive power control; Matlab simulation; Simulink simulation; active filter control strategy; harmonic distortion; line neutral current control; power active filter installation effect; power supply system; pqr instantaneous power concept; reactive power control; three-phase four-wire distribution network; Active filters; Circuit simulation; Computer languages; Harmonic distortion; Inductance; Power harmonic filters; Power system harmonics; Reactive power; Reactive power control; Substations; Matlab-model; Power active filter; efficiency;
fLanguage
English
Publisher
ieee
Conference_Titel
Micro/Nanotechnologies and Electron Devices, 2009. EDM 2009. International Conference and Seminar on
Conference_Location
Novosibirsk
Print_ISBN
978-1-4244-4571-4
Type
conf
DOI
10.1109/EDM.2009.5174023
Filename
5174023
Link To Document