Harmonic filter design for mixed single-phase three-phase load
Author :
Sutherland, Peter E. ; Hostetter, Gary L. ; Hughes, John W.
Author_Institution :
GE Energy Services, Schenectady, NY
fYear :
2008
fDate :
4-8 May 2008
Firstpage :
1
Lastpage :
9
Abstract :
A metals plant contains large 12-pulse rectifier loads and a single-phase induction melting furnace. Recently, the available fault current from the utility increased by 50% due to line improvements. Previously, the capacitor fuses on the induction furnace blew occasionally and replacing them solved the problem. After the utility line improvements, replacing the fuses does not solve the problem, and there are high harmonics throughout the system. Power and harmonic measurements were taken at all significant loads over a period of time to capture the operational cycle of the plant. The system was simulated in EMTP as a three-phase, three-wire system with the single-phase load included. A harmonic filter was designed to mitigate the resonance problem. The design was simulated and validated using the EMTP model.
Keywords :
active filters; integrated circuit design; rectifying circuits; harmonic filter design; harmonic measurement; mixed single-phase three-phase load; power measurement; Capacitors; EMTP; Fault currents; Furnaces; Fuses; Harmonic filters; Power harmonic filters; Power measurement; Power system harmonics; Rectifiers; component; harmonic analysis; harmonic filter design; induction furnace;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industrial and Commercial Power Systems Technical Conference, 2008. ICPS 2008. IEEE/IAS
Conference_Location :
Clearwater Beach, FL
Print_ISBN :
978-1-4244-2093-3
Electronic_ISBN :
978-1-4244-2094-0
Type :
conf
DOI :
10.1109/ICPS.2008.4606283
Filename :
4606283
Link To Document :
بازگشت