    Evaluation of the distributed generators frequency protection due to changes in the anti-islanding requirements

  • Author

    Vieira, Jose C M ; Freitas, Walmir ; Xu, Wilsun ; Morelato, Andre

  • Author_Institution
    Dept. of Electr. Energy Syst., State Univ. of Campinas
  • fYear
    0
  • fDate
    0-0 0
  • Abstract
    This paper analyses the performance of the distributed generator frequency protection if the time required for islanding detection (this is the utility anti-islanding requirement) is increased. Such analysis considers synchronous generators and three types of frequency-based relays: vector surge, rate of change of frequency and under/over frequency relays. Moreover, the concept of performance curves of frequency-based relays is employed. The results show that increasing the time required for islanding detection can improve substantially the islanding detection capability if proper devices and settings are used
  • Keywords
    distributed power generation; power generation protection; relay protection; synchronous generators; antiislanding requirements; distributed generators frequency protection; frequency-based relays; islanding detection; synchronous generators; vector surge; Computational modeling; Distributed power generation; Frequency; Performance analysis; Personnel; Power system relaying; Protective relaying; Relays; Surge protection; Synchronous generators; distributed generation; frequency relays; islanding; protection; synchronous generator;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society General Meeting, 2006. IEEE
  • Conference_Location
    Montreal, Que.
  • Print_ISBN
    1-4244-0493-2
  • Type

    conf

  • DOI
    10.1109/PES.2006.1709317
  • Filename
    1709317