Abstract :
This paper discusses measurements taken on fluorescent lights in the frequency range between 2 and 150 kHz. The presentation of the measurement results form an important part of the paper. The measurement results are presented in time-domain, in the frequency domain and in the time-frequency domain (by means of a "spectrogram"). The latter allows the study of sub-cycle changes in the current spectrum. The current taken by one lamp is compared with the current taken by two, three and four lamps. The relative high-frequency distortion reduced for frequencies above 15 kHz
Keywords :
electric current measurement; fluorescent lamps; time-frequency analysis; 2 to 150 kHz; current measurement; fluorescent lights; high-frequency distortion; time-frequency domain; Current measurement; Electromagnetic compatibility; Electronic ballasts; Fluorescence; Fluorescent lamps; Frequency measurement; Power harmonic filters; Power system harmonics; Time domain analysis; Voltage; Electromagnetic compatibility (EMC); Power quality; Short-time Fourier transform; energy-efficient lighting;