Abstract :
Power transformer´s de-energization leaves the transformer core in a state of magnetization, called residual flux. The presence of this residual flux may induce inrush current which can cause damages on the equipments and system disturbances. In recent years, studies on power transformer´s controlled switching have been carried out to reduce this effect. The purpose of this paper is to emphasize the calculation of residual flux with CVT (Capacitive Voltage Transformer) measurement, using EMTP, during the de-energization of no loaded power transformer. Measuring and integrating directly the CVT´s voltage output may provide a false flux value.
Keywords :
EMTP; magnetisation; potential transformers; power transformers; CVT measurement; EMTP; capacitive voltage transformer; controlled switching; de-energization; magnetization; power transformer; residual flux; system disturbance; transformer core; Circuit breakers; EMTP; Integrated circuit modeling; Power transformers; Switches; Voltage measurement; CVT; EMTP; Power transformer; residual flux compensation;