Abstract :
Stationary lead acid batteries can experience temperature differences within a string especially when operated as 110 V or 480 V back-up batteries. In the present study the influence of a ∼3°C temperature difference on the corrosion induced capacity loss of VRLA monoblocs during 7 and 9 years of float operation in a 5 tier rack installation is reported. Corrosion sensitive VRLA monoblocs can have residual capacity values ranging all the way from 3% to 110% in the same string due the cumulative influence of such minor temperature differences. VRLA cells and monoblocs in which positive grid corrosion has been designed-out as main failure mode, show a much more robust performance under these adverse conditions.
Keywords :
corrosion; emergency power supply; failure analysis; lead acid batteries; life testing; Pb; VRLA life test; VRLA monoblocs; back-up batteries; corrosion induced capacity loss; corrosion sensitive; failure mode; positive grid corrosion; stationary lead acid batteries; temperature difference; Aluminum alloys; Batteries; Corrosion; Lead; Life estimation; Life testing; Qualifications; Rails; Temperature sensors; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Telecommunications Energy Conference, 2004. INTELEC 2004. 26th Annual International
Print_ISBN :
0-7803-8458-X
Type :
conf
DOI :
10.1109/INTLEC.2004.1401485
Filename :
1401485
Link To Document :
بازگشت