Abstract :
This paper provides a statistical analysis of different strategies for no load power transformer´s controlled switching. Especially for the reclosing strategy with residual flux, the combined effects of mechanical timing deviation and pre-arc phenomenon have to be taken into account in the algorithm of optimum reclosing instant. Then, with a single phase power transformer model, we compare this strategy with reclosing strategy based on a preceding controlled de-energization using EMTP multiples simulations under a random mechanical time.
Keywords :
EMTP; HVAC; circuit breakers; optimal control; power system control; power transformers; statistical analysis; switching circuits; EMTP multiples simulation; circuit breaker; mechanical timing deviation; optimum reclosing instant algorithm; power transformer controlled switching; pre-arc phenomenon; reclosing strategy; residual flux; single phase power transformer model; statistical analysis; Circuit breakers; Circuit faults; Integrated circuit modeling; Power transformers; Surges; Switches; EMTP; Power transformer; circuit breaker; controlled switching; statistics;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Control Applications (CCA), 2010 IEEE International Conference on
Conference_Location :
Yokohama
Print_ISBN :
978-1-4244-5362-7
Electronic_ISBN :
978-1-4244-5363-4
Type :
conf
DOI :
10.1109/CCA.2010.5611297
Filename :
5611297
Link To Document :
بازگشت